6ES7515-2RM00-0AB0 S7-1500R CPU 1515R-2 PN CPU with work memory 500 KB for program and 3 MB for data
SIMATIC S7-1500R, CPU 1515R-2 PN central processing unit with work memory 500 KB for program and 3 MB for data, 1st interface: PROFINET RT with 2-port switch, 2nd interface: PROFINET, SIMATIC Memory Card required
Overview
-
The CPU for applications with medium/high requirements for program scope, networking and processing speed, and with increased requirements for availability.
-
High processing speed for binary and floating-point arithmetic
-
Used as central controller with distributed I/O
-
PROFINET IO RT interface with 2-port switch
-
Additional PROFINET interface with separate IP address
-
PROFINET IO controller for operating distributed I/O on PROFINET
Note:
SIMATIC Memory Card required for operation of the CPU
Application
The CPU 1515R-2 PN is the CPU with a large program and data memory for applications which have higher requirements for availability compared with standard CPUs. It can be used as the PROFINET IO controller. The integrated PROFINET IO RT interface is configured as a 2-port switch, enabling a ring topology required for SIMATIC S7-1500R to be set up in the system. The additional integrated PROFINET interface with separate IP address can be used, for example, for network separation.
Design
The CPU 1515R-2 PN features:
-
A powerful processor:
The CPU achieves a command execution time as low as 60 ns per binary command.
-
Large work memory:
500 KB for program, 3 MB for data
-
SIMATIC Memory Cards as load memory
-
Display with functions for:
-
Display of overview information such as station name, higher level designation, location designation, etc.
-
Presenting diagnostic information
-
Display of module information
-
Showing display settings
-
Setting IP addresses
-
Setting date and time
-
Displaying operating mode (redundant or non-redundant)
-
Displaying status (stop, primary or backup)
-
Resetting of CPU to factory settings
-
Disabling/enabling the display
-
Enabling protection levels
-
PROFINET IO RT interface for connecting distributed I/O via PROFINET
Function
-
Performance
-
Faster command processing, language extensions and new data types depending on the CPU type
-
Even shorter response times of the CPUs due to considerably faster backplane bus
-
Powerful network connection:
Each CPU is equipped with PROFINET IO RT (2-port switch) as the standard interface.
-
Security Integrated
-
Password-based know-how protection against unauthorized read-out and modification of program blocks
-
Copy protection for tying individual blocks to the serial number of the SIMATIC Memory Card: The block can only run if the configured memory card is inserted into the CPU.
-
4-level authorization concept:
Communication to the HMI devices can also be restricted.
-
Manipulation protection:
The controller recognizes changed or unauthorized transmissions of the engineering data.
-
Design and handling
-
Display of overview information:
E.g. Station name, plant identifier, location designation, etc., diagnostic information, module information, display settings.
-
Possible operations on the display:
set addresses, set date and time, select operating mode of CPU, reset CPU to factory settings, disable/enable display, activate protection levels.
-
Integrated system diagnostics
-
System diagnostics information is displayed consistently and in plain text in the display, TIA Portal, HMI devices and Web server, even for messages from the drives, and updated even if the CPU is in STOP mode.
-
Integrated in the firmware of the CPU, no special configuration is required
-
SIMATIC Memory Card (required for operation of the CPU)
-
Used as a plug-in load memory or for updating the firmware.
-
Also for storing additional documents or csv files (for recipes and archives)
-
Programming of the standard program section
-
Programming with STEP 7 V15.1
Data sheet 6ES7515-2RM00-0AB0
|
SIMATIC S7-1500R, CPU 1515R-2 PN central processing unit with work memory 500 KB for program and 3 MB for data, 1st interface: PROFINET RT with 2-port switch, 2nd interface: PROFINET, SIMATIC Memory Card required
|
|
|
General information
|
|
Product type designation
|
CPU 1515R-2 PN
|
HW functional status
|
FS01
|
Firmware version
|
V2.9
|
Product function
|
|
Yes; I&M0 to I&M3
|
|
No
|
Engineering with
|
-
STEP 7 TIA Portal configurable/integrated from version
|
V17 (FW V2.9) / V16 (FW V2.8) / V15.1 (FW V2.6)
|
Display
|
Screen diagonal [cm]
|
6.1 cm
|
Control elements
|
Number of keys
|
6
|
Mode selector switch
|
1
|
Supply voltage
|
Rated value (DC)
|
24 V
|
permissible range, lower limit (DC)
|
19.2 V
|
permissible range, upper limit (DC)
|
28.8 V
|
Reverse polarity protection
|
Yes
|
Mains buffering
|
-
Mains/voltage failure stored energy time
|
5 ms
|
Input current
|
Current consumption (rated value)
|
0.8 A
|
Inrush current, max.
|
2.4 A
|
I²t
|
0.02 A²·s
|
Power loss
|
Power loss, typ.
|
6.3 W
|
Memory
|
Number of slots for SIMATIC memory card
|
1
|
SIMATIC memory card required
|
Yes
|
Work memory
|
-
integrated (for program)
|
500 kbyte
|
-
integrated (for data)
|
3 Mbyte
|
Load memory
|
-
Plug-in (SIMATIC Memory Card), max.
|
32 Gbyte
|
Backup
|
|
Yes
|
CPU processing times
|
for bit operations, typ.
|
60 ns
72 ns
96 ns
384 ns
|
for word operations, typ.
|
for fixed point arithmetic, typ.
|
for floating point arithmetic, typ.
|
CPU-blocks
|
Number of elements (total)
|
8 000; Blocks (OB, FB, FC, DB) and UDTs
|
DB
|
-
Number range
-
Size, max.
|
Number range: 1 to 59 999
3 Mbyte; For non-optimized block accesses, the max. size of the DB is 64 KB
|
FB
|
-
Number range
-
Size, max.
|
0 ... 65 535
500 kbyte
|
FC
|
-
Number range
-
Size, max.
|
0 ... 65 535
500 kbyte
|
OB
|
-
Size, max.
-
Number of free cycle OBs
-
Number of time alarm OBs
-
Number of delay alarm OBs
-
Number of cyclic interrupt OBs
-
Number of process alarm OBs
-
Number of startup OBs
-
Number of asynchronous error OBs
-
Number of synchronous error OBs
-
Number of diagnostic alarm OBs
|
500 kbyte
100
20
20
20
50
100
4
2
1
|
Nesting depth
|
|
24
|
Counters, timers and their retentivity
|
S7 counter
|
|
2 048
|
Retentivity
|
- adjustable
|
Yes
|
IEC counter
|
|
Any (only limited by the main memory)
|
Retentivity
|
- adjustable
|
Yes
|
S7 times
|
|
2 048
|
Retentivity
|
- adjustable
|
Yes
|
IEC timer
|
|
Any (only limited by the main memory)
|
Retentivity
|
- adjustable
|
Yes
|
Data areas and their retentivity
|
Retentive data area (incl. timers, counters, flags), max.
|
512 kbyte
|
Flag
|
-
Size, max.
-
Number of clock memories
|
16 kbyte
8; 8 clock memory bit, grouped into one clock memory byte
|
Data blocks
|
-
Retentivity adjustable
-
Retentivity preset
|
Yes
No
|
Local data
|
-
per priority class, max.
|
64 kbyte; max. 16 KB per block
|
Address area
|
Number of IO modules
|
4 096; max. number of modules / submodules
|
I/O address area
|
|
32 kbyte; All inputs are in the process image
|
per integrated IO subsystem
-
-
Inputs (volume)
-
Outputs (volume)
|
32 kbyte; All outputs are in the process image
|
|
8 kbyte
8 kbyte
|
Subprocess images
|
-
Number of subprocess images, max.
|
32
|
Hardware configuration
|
Number of distributed IO systems
|
1
|
Number of IO Controllers
|
|
1
|
Time of day
|
Clock
|
-
Type
-
Backup time
-
Deviation per day, max.
|
Hardware clock
6 wk; At 40 °C ambient temperature, typically 10 s; Typ.: 2 s
|
Operating hours counter
|
|
16
|
Clock synchronization
|
-
supported
-
on Ethernet via NTP
|
Yes
Yes
|
Interfaces
|
Number of PROFINET interfaces
|
2
|
1. Interface
|
Interface types
|
-
RJ 45 (Ethernet)
-
Number of ports
-
integrated switch
|
Yes; X1 2
Yes
|
Protocols
|
-
IP protocol
-
PROFINET IO Controller
-
PROFINET IO Device
-
SIMATIC communication
-
Open IE communication
-
Web server
-
Media redundancy
|
Yes; IPv4 Yes
No
Yes; Only Server Yes
No
Yes
|
PROFINET IO Controller
|
Services
|
-
PG/OP communication
-
Isochronous mode
-
IRT
-
PROFIenergy
-
Number of connectable IO Devices, max.
-
Updating times
|
Yes No No Yes 64
The minimum value of the update time also depends on communication
share set for PROFINET IO, on the number of IO devices, and on the quantity of configured user data
|
Update time for RT
|
- for send cycle of 1 ms
|
1 ms to 512 ms
|
2. Interface
|
Interface types
|
-
RJ 45 (Ethernet)
-
Number of ports
-
integrated switch
|
Yes; X2 1
No
|
Protocols
|
-
IP protocol
-
PROFINET IO Controller
-
PROFINET IO Device
-
SIMATIC communication
-
Open IE communication
-
Web server
-
Media redundancy
|
Yes; IPv4 No
No
Yes; Only Server Yes
No
No
|
Shenzhen Aimiqu Technology Co., Ltd
is a high-tech enterprise integrating industrial control product sales, automation engineering design, development and transformation. There are reliable teams with our company, for a variety of industries automation process control needs, to provide reliable, efficient services and automation overall solution.
established in March 2016, the business scope including general management project is automation equipment accessories, instruments and meters, valves, switches, electronic semiconductor, electronic products, digital products, electronic components, communications products, computer software and hardware, security equipment, energy conservation and environmental protection products, intelligent household products; Operating electronic commerce; Domestic trade, import and export of goods and technology. Electrical automation import and export trade for the main business.
Since its establishment, Aimiqu has been providing industrial automation services, providing customers with high-quality products and automation solutions. In the long-term business process, Emicic has established good partnerships with well-known international manufacturers .
At the same time, attaches great importance to product research and development, invested a lot of funds, independent production and development of electrical equipment such as power distribution cabinet and put into use. For customers in product performance testing, automated production lines, electronic equipment, wire and cable, and other aspects of energy saving equipment reform and development, design, transform the multitude of automation equipment and automation control system, and provide a reliable and professional support, and pre-sale, sale and after-sale services - dragon, by the customer the consistent high praise.